Acti9 IC40a modular circuit breaker 1P+N 2A curve C 4500A/6kA - A9P52602

DESCRIPTION

 

Main Range Acti9
Product Name Acti9 iC40
Product Type Miniature Circuit Breaker
Device Name IC40
Application Distribution
Poles Description 1P + N
Number of Protected Poles 1
Neutral Pole Position Left
Rated Operational Current (In) 2 A
Network Type AC
Tripping Type Thermal-magnetic
Tripping Curve C
Breaking Capacity Code A
Breaking Capacity 6 kA at 230 V AC 50/60 Hz (EN/IEC 60947-2), 4.5 kA at 230 V AC 50/60 Hz (EN/IEC 60898-1)
Isolation Capability Yes (EN/IEC 60947-2)
Quality Labels IMQ
Standards EN/IEC 60898-1, EN/IEC 60947-2
Product Certifications CE, BV, RINA, DNV
Degree of Protection (IP) IP20 (IEC 60529), IP40 (modular enclosure - IEC 60529)
Pollution Degree 3 (EN/IEC 60947-2)
Relative Humidity 95% at 55°C
Operating Altitude 2000 m
Operating Temperature -25…70°C
Storage Temperature -40…85°C
Environmental Sustainability Green Premium Product
REACh Regulation Reference contains no SVHC above threshold
RoHS EU Directive Compliant
Mercury-Free Yes
RoHS Exemptions Information Yes
China RoHS Regulation Out of scope, substance declaration for information
Environmental Profile WEEE: In the EU market, product must be disposed of according to specific waste collection procedures and should not be discarded in household waste.
Network frequency 50/60 Hz
[Ue] Rated operational voltage 230 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In in accordance with EN/IEC 60898-1, 8 x In +/- 20 % in accordance with EN/IEC 60947-2
[Ics] Service breaking capacity 4500 A 100 % Icn at 230 V AC 50/60 Hz in accordance with EN/IEC 60898-1, 75 % 4.5 kA in accordance with EN/IEC 60947-2 Icu
Limitation class EN/IEC 60898-1 3
[Ui] Insulation voltage 400 V AC 50/60 Hz in accordance with EN/IEC 60947-2
[Uimp] Impulse withstand voltage 4 kV in accordance with EN/IEC 60947-2
Fully visible breaking Yes
Control type By handle
Voltage indication ON/OFF indication
Tripping signal Yes
Installation mode Snap-on
Mounting support DIN rail
Pitch of 9 mm 2
Height 85 mm
Width 18 mm
Depth 74 mm
Product weight 120 g
Color White
Mechanical endurance 20000 cycles
Electrical endurance 20000 cycles
Optional locking Locking device
Connection type Tunnel type terminals, top or bottom 1…10 mm² flexible, Tunnel type terminals, top or bottom 1…16 mm² rigid
Wire stripping length 14 mm for top or bottom connection
Tightening torque Top or bottom 2 N.m
Differential protection Separate block
Compatibility code IC40
Code EAN: 3606481324337