DESCRIPTION

Device application: Distribution
Range: Acti 9
Product name: Acti 9 iC60
Product or component type: Miniature circuit-breaker
Device short name: IC60N
Poles description: 1P
Number of protected poles: 1
[In] rated current: 10 A
Network type: ACDC
Trip unit technology: Thermal-magnetic
Curve code: C
Breaking capacity: 10 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz20 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz6000 A Icn conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz10 kA Icu conforming to EN/IEC 60947-2 - 60...72 V DC15 kA Icu conforming to EN/IEC 60947-2 - 12...60 V DC36 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz
Utilisation category: Category A conforming to EN 60947-2Category A conforming to IEC 60947-2
Suitability for isolation: Yes conforming to EN 60947-2Yes conforming to IEC 60947-2Yes conforming to EN 60898-1Yes conforming to IEC 60898-1
Standards: IEC 60947-2EN 60947-2IEC 60898-1EN 60898-1
Quality labels: NF
Network frequency: 50/60 Hz
Magnetic tripping limit: 8 x In +/- 20 %
[Ics] rated service breaking capacity: 10 kA 100 % x Icu conforming to EN 60947-2 - 72 V DC10 kA 100 % x Icu conforming to IEC 60947-2 - 72 V DC6000 A 100 % x Icu conforming to IEC 60898-1 - 230 V AC 50/60 Hz15 kA 100 % x Icu conforming to EN 60947-2 - 12...60 V DC15 kA 100 % x Icu conforming to IEC 60947-2 - 12...60 V DC6000 A 100 % x Icu conforming to EN 60898-1 - 230 V AC 50/60 Hz27 kA 75 % x Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz27 kA 75 % x Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz15 kA 75 % x Icu conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz15 kA 75 % x Icu conforming to EN 60947-2 - 100...133 V AC 50/60 Hz
Limitation class: 3 conforming to EN 60898-13 conforming to IEC 60898-1
[Ui] rated insulation voltage: 500 V AC 50/60 Hz conforming to IEC 60947-2500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage: 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2
Contact position indicator: Yes
Control type: Toggle
Local signalling: Trip indicator
Mounting mode: Fixed
Mounting support: DIN rail
Comb busbar and distribution block compatibility: YES top or bottom
9 mm pitches: 2
Height: 85 mm
Width: 18 mm
Depth: 78.5 mm
Product weight: 0.215 kg
Colour: White
Mechanical durability: 20000 cycles
Electrical durability: 10000 cycles
Connections - terminals: Single terminal, top or bottom rigid wire(s) 1...25 mm² maxSingle terminal, top or bottom flexible wire(s) 1...16 mm² max
Wire stripping length: 14 mm top or bottom
Tightening torque: 2 N.m top or bottom
Earth-leakage protection: Without
IP degree of protection: IP20 conforming to EN 60529IP20 conforming to IEC 60529
Pollution degree: 3 conforming to EN 60947-23 conforming to IEC 60947-2
Overvoltage category: IV
Tropicalisation: 2 conforming to IEC 60068-1
Relative humidity: 95 % ( 55 °C )
Operating altitude: 0...2000 m
Ambient air temperature for operation: -35...70 °C
Ambient air temperature for storage: -40...85 °C
Warranty period: 18 months
Sustainable offer status: Green Premium productRoHS (date code: YYWW)
Code EAN: 3606480079467
Contexte:

With exclusive features, the Acti 9 iC60 DIN rail MCB is definitely geared to absolute safety and improved continuity of service.

  • VisiSafe : for safe operation and maintenance work on circuits.
  • Class-2 insulation : continuous safety for operators and unqualified personnel.
  • VisiTrip : detects faulty Miniature Circuit-Breaker outgoers quickly and reduces intervention time.
  • Add-on fully immune earth leakage protection devices : better continuity of service, especially in polluted environments and networks.
  • Nominal current: 1 to 63 A
  • Large choice of breaking capacities up to 100 kA and tripping curves: B, C, D, Compliance with standards IEC/EN 60898 or IEC/EN 60947-2,
  • Full coordination with Acti 9 range Residual Current Devices (RCDs) and Compact NSX Moulded Case Circuit Breakers (MCCBs), 
  • Suitable for isolation in accordance with industrial standard IEC 60947
  • Operating voltage: up to 440 V AC, insulation voltage: 500 V
  • Optional add-on earth leakage modules: iC60 Vigi, 
  • Optional auxiliaries: indication of state and tripping, shunt tripping, undervoltage tripping, overvoltage tripping,