Bloc différentiel Vigi NG125 80-125A Tetra 440-500V - 19049
DESCRIPTION
| Product or component type: | Add-on residual current devices |
|---|---|
| Device short name: | Vigi NG125 |
| Poles description: | 4P |
| [In] rated current: | 125 A |
| Network type: | AC |
| Earth-leakage sensitivity: | 1000 mA3000 mA300 mA500 mA |
| Earth-leakage protection time delay: | Adjustable instantaneous/selective/delayed |
| Earth-leakage protection class: | Class A |
| Quality labels: | NF |
| Device location in system: | Outgoer |
|---|---|
| Network frequency: | 50/60 Hz |
| [Ue] rated operational voltage: | 230...415 V AC 50/60 Hz |
| Residual current tripping technology: | Voltage independent |
| [Ui] rated insulation voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-2 |
| Mounting mode: | Fixed |
| Mounting support: | 35 mm symmetrical DIN rail |
| Electrical connection to mcb: | By screws |
| 9 mm pitches: | 11 |
| Height: | 118 mm |
| Width: | 207 mm |
| Depth: | 81 mm |
| Product weight: | 0.8 kg |
| Connections - terminals: | Tunnel type terminals rigid wire(s) 16...70 mm² maxTunnel type terminals flexible wire(s) 10...50 mm² max |
| Wire stripping length: | 20 mm |
| Tightening torque: | 6 N.m |
| Standards: | IEC 60947-2 |
|---|---|
| IP degree of protection: | IP20 conforming to IEC 60947-2 |
| Pollution degree: | 3 conforming to IEC 60947-2 |
| Electromagnetic compatibility: | 8/20 µs impulse withstand, 5000 A conforming to IEC 60947-2 |
| Ambient air temperature for operation: | -25...60 °C |
| Ambient air temperature for storage: | -40...85 °C |
| Warranty period: | 18 months |
| Code EAN: | 3303430190493 |
|---|---|
| Contexte: |
|
| Substitution_texte: | Product not available. Here is the equivalent reference that we offer: 19048 - NG125 - earth leakage add-on block - Vigi NG125 - 4P - 125A - 300mA |