website Skip to content
Schneider Electric ComPacT nouvelle génération circuit breaker ComPacT NSX100M AC/DC, 25 kA at 415 VAC, TMD trip unit 80 A, 2 poles 2d - C10M2TM080
Schneider Electric ComPacT nouvelle génération circuit breaker ComPacT NSX100M AC/DC, 25 kA at 415 VAC, TMD trip unit 80 A, 2 poles 2d - C10M2TM080

circuit breaker ComPacT NSX100M AC/DC, 25 kA at 415 VAC, TMD trip unit 80 A, 2 poles 2d - C10M2TM080

SKU : C10M2TM080

Contact us for price and lead time for this product. Our team will respond quickly.

Lead time: 2–3 weeks – Ships quickly after order confirmation
Estimated Delivery : - .

circuit breaker ComPacT NSX100M AC/DC, 25 kA at 415 VAC, TMD trip unit 80 A, 2 poles 2d - C10M2TM080

DESCRIPTION

Range: ComPacT new generation
Product name: ComPacT NSX new generation
Range of product: ComPacT NSX100...250 new generationComPacT NSX100...250 DC new generation
Device short name: NSX100M
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 2P
Protected poles description: 2D
[In] rated current: 80 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz500 V DC
Network type: ACDC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-225 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-218 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-28 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-285 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
Breaking capacity code: M 25 kA 415 V AC
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit protection functions: LI
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-225 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-225 kA at 440 V AC 50/60 Hz conforming to IEC 60947-218 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-28 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA at 250 V DC 50/60 Hz conforming to IEC 60947-285 kA at 500 V DC 50/60 Hz conforming to IEC 60947-236 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 20000 cycles
Electrical durability: 20000 cycles at 277 V In/210000 cycles at 277 V In
Power dissipation per pole: 8.77 W
Mounting support: Backplate
Mounting position: Horizontal and verticalFlat on the back
Upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L
Trip unit rating: 80 A at 40 °C
Long time pick-up adjustment type Ir: Fixed
Long time pick-up adjustment range: 1 x In
Long time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 640 A
Earth-leakage protection: Without
Width: 70 mm
Height: 161 mm
Depth: 86 mm
Net weight: 1.2 kg
Compatibility code: NSX100
Standards: EN/IEC 60947
Product certifications: CCCEACMarine
Overvoltage category: Class II
Electrical shock protection class: Class II
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
Ambient air temperature for operation: -25...70 °C
Ambient air temperature for storage: -50...85 °C
Relative humidity: 0...95 %
Operating altitude: 0...2000 m without derating2000 m...5000 m with derating
Sustainable offer status: Green Premium productREACh Regulation
Code EAN: 3606481995889