circuit breaker ComPacT NSX100M AC/DC, 40 kA at 240 VAC, TMD trip unit 63 A, 1 pole 1d - C10M1TM063
DESCRIPTION
| Range: | ComPacT new generation |
|---|---|
| Product name: | ComPacT NSX new generation |
| Range of product: | ComPacT NSX100...250 new generationComPacT NSX100...250 DC new generation |
| Device short name: | NSX100M |
| Product or component type: | Circuit breaker |
| Device application: | Distribution |
| Poles description: | 1P |
| Protected poles description: | 1D |
| [In] rated current: | 63 A at 40 °C |
| [Ue] rated operational voltage: | 277 V AC 50/60 Hz250 V DC 50/60 Hz |
| Network type: | ACDC |
| Network frequency: | 50/60 Hz |
| Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
| Utilisation category: | Category A |
| Breaking capacity: | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 250 V DC conforming to IEC 60947-2 |
| Breaking capacity code: | M 40 kA 240 V AC |
| Trip unit name: | TM-D |
| Trip unit technology: | Thermal-magnetic |
| Trip unit protection functions: | LI |
| Control type: | Toggle |
| Mounting mode: | Fixed |
| [Ui] rated insulation voltage: | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity: | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-285 kA at 250 V DC conforming to IEC 60947-2 |
| Mechanical durability: | 20000 cycles |
| Electrical durability: | 20000 cycles at 277 V In/210000 cycles at 277 V In |
| Power dissipation per pole: | 8.61 W |
| Mounting support: | Backplate |
| Mounting position: | Horizontal and verticalFlat on the back |
| Upside connection: | Front |
| Downside connection: | Front |
| Connection pitch: | 35 mm |
| Protection type: | L |
| Trip unit rating: | 63 A at 40 °C |
| Long time pick-up adjustment type Ir: | Fixed |
| Long time pick-up adjustment range: | 1 x In |
| Long time delay adjustment type: | Fixed |
| Instantaneous pick-up adjustment type Ii: | Fixed |
| Instantaneous pick-up adjustment range: | 500 A |
| Earth-leakage protection: | Without |
| Width: | 35 mm |
| Height: | 161 mm |
| Depth: | 86 mm |
| Net weight: | 0.7 kg |
| Compatibility code: | NSX100 |
| Standards: | EN/IEC 60947 |
|---|---|
| Product certifications: | CCCEACMarine |
| Overvoltage category: | Class II |
| Electrical shock protection class: | Class II |
| Pollution degree: | 3 conforming to IEC 60664-1 |
| IP degree of protection: | IP40 conforming to IEC 60529 |
| IK degree of protection: | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation: | -25...70 °C |
| Ambient air temperature for storage: | -50...85 °C |
| Relative humidity: | 0...95 % |
| Operating altitude: | 0...2000 m without derating2000 m...5000 m with derating |
| Sustainable offer status: | Green Premium productREACh Regulation |
| Code EAN: | 3606481995780 |
|---|